If you have been searching for SW262 of Circuit Breaker components with NSN 5925000618178 under FSC 5925 Circuit Breakers, look no further than Limitless Aerospace. SW262 part is listed alongside the other Circuit Breaker parts, and it has been manufactured by The Technical Material Corporation (CAGE Code 82679). With current availability through our website, we invite you to request a quick and competitive quote for SW262 by filling out and submitting the RFQ form below. By providing us with information such as your target price and when you need your parts by, we can ensure that we offer a personalized solution that accommodates your individual needs and requirements.
NSN parts are those that follow the NSN system as dictated by the NATO Standardization Agreements, and they contain a 13-digit serial number to optimize the procurement, stocking, and issuing of items through the federal supply system. On Limitless Aerospace, we make finding the NSN parts and components you need easy, and customers may peruse our robust NSN part catalogues or use our search engine to find specific items with ease. As the only independent distributor with a no China sourcing pledge, we choose to only stock items from top global manufacturers such as The Technical Material Corporation. Get started on the purchasing process for SW262 today and see how we can serve as your strategic sourcing partner for all of your operational needs.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-061-8178 Item Description: Circuit Breaker | 5925 | 000618178 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Sw262 | 2 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | SINGLE POLE TYPE |
ADAQ | BODY LENGTH | 2.500 INCHES NOMINAL |
ADAT | BODY WIDTH | 0.750 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.125 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.547 INCHES NOMINAL |
AKPX | POLE QUANTITY | 1 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 1.010 MINIMUM SINGLE LOCATION AND 5.450 MAXIMUM SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.250 MINIMUM AT 200 PCT SINGLE LOCATION AND 0.800 MAXIMUM AT 200 PCT SINGLE LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 48.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
Don’t forget That If You’d Ever Like a Quote for Parts Within 15 Minutes or Less, You Can Fill out the Instant RFQ form On this Website’S Homepage.