If you have been searching for 10M28-704 of Chiller Water Refri components with NSN 4130001138232 under FSC 4130 Refrigeration and Air Condition Components, look no further than Limitless Aerospace. 10M28-704 part is listed alongside the other Chiller Water Refri parts, and it has been manufactured by Carrier Corporation (CAGE Code 10855). With current availability through our website, we invite you to request a quick and competitive quote for 10M28-704 by filling out and submitting the RFQ form below. By providing us with information such as your target price and when you need your parts by, we can ensure that we offer a personalized solution that accommodates your individual needs and requirements.
NSN parts are those that follow the NSN system as dictated by the NATO Standardization Agreements, and they contain a 13-digit serial number to optimize the procurement, stocking, and issuing of items through the federal supply system. On Limitless Aerospace, we make finding the NSN parts and components you need easy, and customers may peruse our robust NSN part catalogues or use our search engine to find specific items with ease. As the only independent distributor with a no China sourcing pledge, we choose to only stock items from top global manufacturers such as Carrier Corporation. Get started on the purchasing process for 10M28-704 today and see how we can serve as your strategic sourcing partner for all of your operational needs.
MRC | Criteria | Characteristic |
---|---|---|
AWWH | WATER SIDE TEST MINIMUM PRESSURE | 225.0 POUNDS PER SQUARE INCH |
AWGH | TUBE TYPE | STRAIGHT |
AWKZ | WATER CONNECTION SIZE | 2-1/2 IN. N STD |
AWLA | REFRIGERANT INLET CONNECTION SIZE | 1-5/8 IN. |
AWLB | REFRIGERANT OUTLET CONNECTION QUANTITY | 2 |
ABHP | OVERALL LENGTH | 89.000 INCHES NOMINAL |
SR-5 | DESIGN CONTROL REFERENCE | 10M28-704 |
AWWG | REFRIGERANT SIDE TEST MINIMUM PRESSURE | 225.0 POUNDS PER SQUARE INCH |
AEUG | SHELL MATERIAL | BRASS |
SR-5 | MANUFACTURERS CODE | 10855 |
ABMK | OVERALL WIDTH | 16.875 INCHES NOMINAL |
AWCD | WATER FOR WHICH DESIGNED | FRESH |
AWCK | REFRIGERANT OPERATING LOCATION | IN TUBES |
ZZZY | REFERENCE NUMBER DIFFERENTIATING CHARACTERISTICS | FOR25 TON NONMAGNETIC AIR CONDITIONING PLANT |
ACKL | MEDIA FOR WHICH DESIGNED | REFRIGERANT 12 |
AWGF | EFFECTIVE COOLING AREA | 169.000 SQUARE FEET |
AWGJ | TUBE MATERIAL | COPPER |
AWKR | SHELL LENGTH | 6.500 FEET |
AWKS | SHELL OUTSIDE DIAMETER | 12.875 INCHES |
AWKT | WATER CONNECTION QUANTITY | 2 |
AWKW | WATER CONNECTION TYPE | FLANGE |
AWKX | REFRIGERANT INLET CONNECTION QUANTITY | 1 |
AWKY | REFRIGERANT INLET CONNECTION TYPE | TUBE |
AWLC | REFRIGERANT OUTLET CONNECTION TYPE | TUBE |
AWLD | REFRIGERANT OUTLET CONNECTION SIZE | 2-5/8 IN. |
ADSM | MOUNTING POSITION | HORIZONTAL |
SR-5 | THE MANUFACTURERS DATA |
Don’t forget That If You’d Ever Like a Quote for Parts Within 15 Minutes or Less, You Can Fill out the Instant RFQ form On this Website’S Homepage.
Request for Quote